Repalcing a DDN SFA10K or 12K controller

Permanently deleted user -

Replacing a SFA10K or SFA12K Controller

NOTE : This procedure does NOT apply to the E-platforms. Controller replacement
on the E-platforms should be handled by DDN field engineers only.
If, during the course of a problem determination, authorized support channels determine
that a controller is faulty and must be replaced, use the procedure below to perform a
controller replacement:


1. Secure a copy of the firmware file of currently installed SFA OS firmware version.
It is best practice to obtain the firmware image file matching the currently installed
version on the controller to be replaced. Firmware images can be requested from DDN
Technical Support.


2. Verify the physical location of the controller to be replaced.
If the controller to be replaced is responsive to CLUI commands, log in to the controller
via ssh and run the command LOCATE CONTROLLER LOCAL. This will blink the
Locate LED on the controller.
NOTE : If the controller is unresponsive, guidance from DDN Technical Support
should be sought.
The duration of the Locate LED blink period is configurable. By default, the duration is
two minutes. If you need to increase the locate dwell time, refer to Section 4.12.1,
"Locate Dwell Time" for information.

SET SUBSYSTEM LOCATE_DWELL_TIME
SHOW SUBSYSTEM ALL to see the current dwell time value.

3. Optional: DDN recommends you create an event log entry to record the controller
replacement service action.
Log in to the healthy controller and use the MARK command to create a user event log
entry similar to the example below:
MARK CONTROLLER LOCAL TEXT “Controller replacement service action
initiated”
Change the text in the above example as required.

4. Capture the subsystem configuration information prior to the service action.
It is best practice to capture and save the output of the following commands in order
to obtain detailed configuration information on the subsystem prior to the service
action. Also capture the same information on the healthy (peer) controller. If only one
controller is responsive, only collect the status information from the healthy controller.
   SHOW SUBSYSTEM SUMMARY
   SHOW SUBSYSTEM SUMMARY ALL
   APP SHOW HOST
   APP SHOW PRESENTATION
   APP SHOW INITIATOR
   APP SHOW DISCOVERED_INITIATOR
   UI SHOW NETWORK LOCAL 0
   UI SHOW EMAIL
   UI SHOW TEMP


5. Shut down the controller to be replaced.
If the controller to be replaced is operational, log in to the controller and issue the
command SHUTDOWN CONTROLLER LOCAL to gracefully shut it down prior to
replacement.


6. Verify that the controller has been shut down by checking the Power LED of the
controller (Figure 420) (Figure 421) and its dedicated BBU.


7. Physically replace the failed controller:
a) Note down the cabling scheme to the controller.
b) Disconnect the cables from the controller.
c) Remove the front bezel.
d) Remove screws or disengage latches that secure the controller to the rack.
e) Slide the controller out from the rack to the point that the slide rails click on each
side and lock into place.
f) Disengage the locking tab on the slide rails to release the controller side rails from
the rack rails.
g) Slide the controller forward until the controller side rails are disengaged from the
rack rails. Place the controller on a sturdy table.
h) Remove the side rails from the old unit and install them on the new controller.
i) Slide the controller side rails into the rack rails by carefully aligning them and
sliding the controller inward towards the rack until they click into the locked
position.
j) Reinstall the screws that secure the controller to the rack.
k) Reinstall the front bezel.
l) Reconnect the cables at the back.

8. Configure the IP address of the replacement controller.
After controller replacement, it is necessary to configure the IP address, SNMP, and
email parameters to match the previous settings.
By default, the FRU replacement controller is configured with IP address 10.0.0.1,
unless noted otherwise. The default IP addresses for complete FRU couplets are
10.0.0.1 for controller 0 and 10.0.1.1 for controller 1. The default subnet mask is class C
(255.255.255.0).
Log in to the controller via its serial port and configure the network interface settings.
Refer to Section 4.17.3, "Change Network Interface Settings" if you need instructions
on how to change the settings.


9. Determine if a firmware update is required on the replacement controller.
If the firmware level on the replacement controller is the same as the version installed
in the subsystem, it will directly become operational after power on and connectivity
tests complete successfully.
If the firmware on the replacement controller has a different version, it will power up
and boot into a offline MIR state: MIR_VERSION_MISMATCH. To clear the MIR state
and bring the replacement controller online, a firmware update will be required. Refer
to Section 6.7.2, "Controller Firmware Update Procedure" for instructions.


10. Power up the replacement controller and verify that it becomes correctly operational.
When matching firmware is installed on the replacement controller, it will attempt to
join the SFA subsystem configuration and validate all cable connections.
If successful, all disks will be recognized by the replacement controller and it will
become operational. Pools will be rebalanced and moved back to their preferred home
RAID processors after a period of up to 10 minutes. It is recommended that an SFA
support contact review the detailed configuration of the subsystem after controller
replacement to validate all key aspects of the status.


11. Initialize the backup battery life remaining feature as described in Section 6.8.4.

Have more questions? Submit a request

0 Comments

Article is closed for comments.